30 March 2000 Improving the results of thermographic inspections of electrical transmission and distribution lines
John R. Snell Jr., Joe Renowden
Author Affiliations +
Abstract
Inspecting compression splices on transmission and distribution lines has long been accomplished using infrared thermography but the results have too often been disappointing. There are instances of splices failing within months of infrared inspections. An understanding of the actual condition of the splices had been `masked' by one or more of the factors discussed in this paper. A number of factors are involved, including a poor understanding of the application of the technology; inadequate training of some service providers; environmental factors; low electrical loading; the resolution limitations of the inspection equipment; low emissivity of the components, and a poor understanding of how to interpret the data.
© (2000) COPYRIGHT Society of Photo-Optical Instrumentation Engineers (SPIE). Downloading of the abstract is permitted for personal use only.
John R. Snell Jr. and Joe Renowden "Improving the results of thermographic inspections of electrical transmission and distribution lines", Proc. SPIE 4020, Thermosense XXII, (30 March 2000); https://doi.org/10.1117/12.381541
Lens.org Logo
CITATIONS
Cited by 2 scholarly publications.