10 November 2022 Study on the coordination strategy of generator loss of excitation protection and low excitation limit
Ming Xiao, Zhaoting Li, Yongfei Ma, Yujie Ding
Author Affiliations +
Proceedings Volume 12331, International Conference on Mechanisms and Robotics (ICMAR 2022); 123311B (2022) https://doi.org/10.1117/12.2653183
Event: International Conference on Mechanisms and Robotics (ICMAR 2022), 2022, Zhuhai, China
Abstract
Generator loss of excitation protection is generally based on the R-X coordinate plane, while the low excitation limit is generally based on the P-Q coordinate plane. Due to the above two are not on the same coordinate plane, the coordination relationship between them cannot be shown intuitively. A0 reduction method suitable for engineering practice is proposed, that is, the setting of loss of excitation protection is mapped from R-X coordinate plane to P-Q coordinate plane. Based on P-Q coordinate plane, generator loss of excitation protection and low excitation limit are calculated, and the correctness of the method is verified with a cooperation of network related protection example of a power plant.
© (2022) COPYRIGHT Society of Photo-Optical Instrumentation Engineers (SPIE). Downloading of the abstract is permitted for personal use only.
Ming Xiao, Zhaoting Li, Yongfei Ma, and Yujie Ding "Study on the coordination strategy of generator loss of excitation protection and low excitation limit", Proc. SPIE 12331, International Conference on Mechanisms and Robotics (ICMAR 2022), 123311B (10 November 2022); https://doi.org/10.1117/12.2653183
Advertisement
Advertisement
RIGHTS & PERMISSIONS
Get copyright permission  Get copyright permission on Copyright Marketplace
KEYWORDS
Magnetism

Transformers

Reliability

Resistance

Iron

Lithium

Medium wave

Back to Top